NSX断路器漏电模块Vigi ME、MH、MB有何区别?
问题描述:
NSX断路器漏电模块Vigi ME、MH、MB的区别是什么?

所属产品线:
Compact NSX

解决方法:

NSX100~160断路器配Vigi ME、MH均可,NSX250只能配VigiMH,NSX400~630只能配Vigi MB。

Vigi ME的灵敏度(300mA)及时间延时(不大于40ms)均固定不可调,而Vigi MH、MB的灵敏度分5档(0.03-0.3-1-3-10A)(0.3-1-3-10-30A) 时间延时分4档(0-60-150-310ms)可以调整。如果灵敏度被设置为30毫安,则脱扣器瞬时脱扣动作。

 